The Insulator
Education Initiative (IEI)
Find Content

RTV-coated ceramic post insulators for HVDC reactors: what the qualification data shows

What engineers and decision makers can learn from the paper: ‘Manufacturing and qualifying RTV-coated ceramic post insulators for a 400 kV HVDC air-core dry-type reactor project’. Plus download the full paper. This paper was presented by ITG/Trench Austria/PPC Insulators at the 2025 INMR World Congress, Panama City, Panama.

Close up of porcelain insulator, Insulator Education Initiative article on RTV coating
Silicone coating hydrophobicity test: hydrophobicity class HC1 as per IEC TS 62073 was observed on all tested samples

What the study found about RTV-coated porelain post insulators for HVDC reactors

Factory-applied RTV coating offers significant advantages over field-applied coating. The controlled factory environment ensures excellent adhesion and homogenous thickness, which ensure a long lifetime.
Isostatic pressing gives the porcelain more strength than the conventional plastic process. The C-130 grade body is pressed at up to 1,100 bar rather than extruded conventionally, which makes it well suited to demanding support-insulator duty.
The factory-applied RTV coating enabled the fulfillment of all specified factory acceptance tests (FATs). Coating thickness came in at an average of 547 µm on the upper shed and 421 µm underneath, against specs of 400 µm and 320 µm. Adhesion scored class 0 (the best result) on ISO 2409, hydrophobicity was rated HC1, and thickness homogeneity (±11% around the shed, ±1% tip-to-core) sat comfortably inside the ±20% tolerance.
Tracking and erosion resistance held up under a 6-hour stress test. Maximum erosion depth across samples was 0.65 mm, with no punctures and no ignition, tested to IEC 60587:2022.
The paper questions the value of the four ‘fingerprint’ characterization tests. TGA, DSC, FTIR and density testing on the raw silicone came back with no defined pass/fail criteria and no interpretation from the accredited lab – the authors note repeatability is poor and that IEC TC/36 is now proposing, in the draft IEC TS 63432, to reclassify these as “for information only” rather than qualification requirements.
Getting the tracking and erosion test done at all was a logistical problem. There was no accredited lab equipped for this and ultimately it was run in Trench Austria’s own material lab.
Key results: The TGA and DSC diagrams showed the RTV was thermally stable from -60°C to +200°C. In the tracking and erosion test, all samples passed with a maximum measured erosion depth of 0.65 mm. None of the samples punctured or ignited.

Manufacturing and qualifying RTV-coated C8-2550 ceramic post insulator for HVDC air-core dry-type reactors

Authors

What’s inside?

This paper documents how an isostatically-pressed, RTV-coated C8-2550 post insulator was manufactured and qualified for a real 500 kV subsea HVDC link. It raises a question about whether some of the standard coating characterization tests actually tell you anything useful.

The paper covers:

1. Context/problem: why HVDC links need bigger, more pollution-resistant post insulators

2. The product: the RTV-coated C8-2550 ceramic post insulator built for a 500 kV subsea HVDC project

3. Manufacturing process: isostatic pressing plus the three-layer RTV coating process

4. Qualification testing: mechanical/electrical type tests plus RTV-specific coating tests

5. A critical point on the ‘fingerprint’ tests: authors question the value of TGA/DSC/FTIR/density testing, flagging the draft IEC TS 63432 direction

6. Standards outlook: no finished standard yet; qualification is currently negotiated project-by-project

“Expect procurement and qualification discussions to start referencing IEC TS 63432 once it’s finalized, and factor that timeline into upcoming HVDC procurement”

What it tells engineers

Mechanical and electrical type testing followed IEC 60168 as standard practice. The real substance of this paper is the RTV coating qualification path, which isn’t governed by a finished standard yet – IEC TS 63432 is still circulating in draft and should be released soon.

On this project, acceptance criteria for thickness, adhesion, hydrophobicity and homogeneity were set by direct agreement between customer and manufacturer, not pulled from an existing spec.

What to do in practice

  • When specifying RTV-coated insulators now, agree thickness, adhesion and homogeneity acceptance criteria directly with the manufacturer rather than assuming a standard covers it
  • Treat TGA, DSC, FTIR and density reports on the coating material as informational rather than pass/fail evidence, in line with where IEC TC/36 is heading
  • Ask whether coating is being applied factory-side or in the field – factory application gave this project tighter, more consistent thickness control
The RTV dry-film coating thickness was specified as 400 µm on upper side of the shed and 320 µm underneath, and passed the test

What it tells decision makers

There’s no finished standard yet for qualifying RTV-coated ceramic post insulators. IEC TS 63432 is out for comment now, and its likely direction – moving several characterization tests to ‘for information only’ – will reshape what factory acceptance testing looks like once it’s adopted.

In the meantime, qualification on projects like this one is being negotiated project by project between manufacturer and customer.

What to do in practice

  • Expect procurement and qualification discussions to start referencing IEC TS 63432 once it’s finalized – factor that timeline into upcoming HVDC procurement
  • Budget for factory-applied RTV coating over field coating where pollution performance and creepage distance are critical – it avoids the cost and complexity of de-energizing a line for on-site work
CAB spray drying process used. Source: PPC Insulators

To sum up: factory-applied RTV coating is superior

This project confirmed that factory-applied RTV coating offers significant advantages over field-applied coating. The controlled factory environment ensures excellent adhesion and homogenous thickness, which are guarantees for a long lifetime.

In contrast, on-site coating is susceptible to dust and rain, more expensive due to substation de-energization, and results in more thickness variation.

The new Technical Specification IEC TS 63432 will reinforce the tendency to use factory-coated ceramic insulators for HVDC applications where high rigidity and pollution performance are required.

Want to hear insulator new, insights and paper summaries as soon as we release them? Sign up to receive IEI updates

References

IEC CD 63432: RTV silicone rubber-coated insulators for AC and DC high-voltage applications – definitions, test methods and acceptance criteria, date of circulation July 11, 2025

IEC 60168:1994 Ed. 4.0: Tests on indoor and outdoor post insulators of ceramic material or glass for systems with nominal voltages greater than 1000 V

EN ISO 11358-1:2022 Ed. 2.0: Plastics – Thermogravimetry (TG) of polymers – Part 1: General principles

EN ISO 11357-2:2022 Ed. 3.0: Plastics – Differential scanning calorimetry (DSC) – Part 2: Determination of glass transition temperature and step height

EN 1767:1999: Products and systems for the protection and repair of concrete structures – Test methods – Infrared analysis

ISO 2781:2018 Ed. 5.0: Rubber, vulcanized or thermoplastic – Determination of density

IEC 60587:2022, Ed. 4.0: Electrical insulating materials used under severe ambient conditions – Test methods for evaluating resistance to tracking and erosion

EN ISO 2409:2020 Ed. 5.0: Paints and varnishes – Cross-cut test

IEC TS 62073:2016 Ed. 2.0: Guidance on the measuremement of hydrophobicity of insulator surfaces

Markku Ruokanen
Group Quality and R&D Director , ITG